• DocumentCode
    3050991
  • Title

    A new method for locating partial discharges in transformers

  • Author

    Steiner, J.P. ; Weeks, W.L.

  • Author_Institution
    Biddle Instrum., Blue Bell, PA, USA
  • fYear
    1990
  • fDate
    28-31 Oct 1990
  • Firstpage
    275
  • Lastpage
    281
  • Abstract
    A novel method for determining the axial location of partial discharges in cast coils is presented. A signal processing algorithm is used to determine the normalized energy as a function of position along the coil. The normalized energy is interpreted in terms of the attenuation of the electromagnetic emissions from the partial discharges along the axis of the transformer. A plot of the attenuation as a function of distance along the length of coil clearly indicates the location of the partial discharges. It is concluded that the asymptotic maximum-likelihood estimate of the energy profile is an effective means for localizing partial discharge sites in the winding sections of a cast coil
  • Keywords
    fault location; partial discharges; power transformers; EM emissions attenuation; asymptotic maximum-likelihood estimate; axial location; cast coils; partial discharge location method; signal processing algorithm; Attenuation; Coils; Electromagnetic measurements; Frequency; Magnetic field measurement; Manufacturing processes; Partial discharge measurement; Partial discharges; Thermal stresses; Transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1990. Annual Report., Conference on
  • Conference_Location
    Pocono Manor, PA
  • Type

    conf

  • DOI
    10.1109/CEIDP.1990.201354
  • Filename
    201354