• DocumentCode
    3052181
  • Title

    The determination of charge behavior at a liquid-solid interface

  • Author

    Nelson, J.K. ; Lee, M.J. ; Kaushik, R.R. ; McMullan, W.J.

  • Author_Institution
    Dept. of Electr. Power Eng., Rensselaer Polytech. Inst., Troy, NY, USA
  • fYear
    1990
  • fDate
    28-31 Oct 1990
  • Firstpage
    684
  • Lastpage
    689
  • Abstract
    A methodology has been developed to provide information on the way in which charges distribute and relax on cellulose surfaces and on their impact on the breakdown of oil-cellulose insulation. Using this approach, not only can the charge be monitored in time, but its spatial distribution can be ascertained. The method has further been extended to apply an interrogating impulse voltage across a charged surface which permits the impact of surface charge on creep breakdown to be determined. Field plots which allow the calculation of a power frequency (capacitive) distribution in the presence of a static charge reveal that the impact of accumulated surface charge on the dielectric integrity of transformer structures is significant and should be considered in design criteria
  • Keywords
    impulse testing; insulating oils; insulation testing; transformer insulation; breakdown; cellulose surfaces; charge behavior; creep breakdown; dielectric integrity; interrogating impulse voltage; liquid-solid interface; oil-cellulose insulation; power frequency distribution; spatial distribution; surface charge; transformer structures; Breakdown voltage; Creep; Electric breakdown; Electrodes; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Stress; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1990. Annual Report., Conference on
  • Conference_Location
    Pocono Manor, PA
  • Type

    conf

  • DOI
    10.1109/CEIDP.1990.201417
  • Filename
    201417