DocumentCode
3053384
Title
Partial discharge diagnosis for transformer — One step toward strong smart grid in China
Author
Zheng, Zhong ; Ruan, Ling ; Li, Chengrong ; Gao, Shengyou ; Ruan, Jiangjun ; Gui, Junfeng
Author_Institution
North China Electr. Power Univ., Beijing, China
fYear
2009
fDate
18-21 Oct. 2009
Firstpage
352
Lastpage
355
Abstract
This paper presented four cases of online/offline partial discharge (PD) diagnosis in various scenarios. Some case gave strong evidence of PD occurrence but no discharge signal was detected. Some case gave obvious PD signal pattern, which was identified as noise. In the last case, a small PD phenomenon was identified and located by a combination of several diagnostic methods, including dissolved gas analysis, leakage current analysis, and PD detection through pulse current signal and ultra sonic signal. The results show that online PD detection was useful but complicate. The information can be conflicting and misleading. A comprehensive understanding of test condition and an in-deep study of the measurement results is essential in such diagnosis.
Keywords
leakage currents; partial discharges; power grids; power transformers; China; PD detection; dissolved gas analysis; leakage current analysis; online-offline partial discharge diagnosis; pulse current signal; smart grid; transformer; ultrasonic signal; Dissolved gas analysis; Fault location; Leak detection; Leakage current; Partial discharges; Signal analysis; Signal detection; Signal processing; Smart grids; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2009. CEIDP '09. IEEE Conference on
Conference_Location
Virginia Beach, VA
ISSN
0084-9162
Print_ISBN
978-1-4244-4557-8
Electronic_ISBN
0084-9162
Type
conf
DOI
10.1109/CEIDP.2009.5377893
Filename
5377893
Link To Document