Title :
Reducing air clearance requirements for voltage uprating of overhead line by use of line surge arresters
Author :
Venkatesan, S. ; Haddad, A. ; Griffiths, H. ; Harid, N. ; Albano, M.
Author_Institution :
High Voltage Energy Syst. Group, Cardiff Univ., Cardiff, UK
Abstract :
While uprating an overhead line to a higher voltage level, it is often difficult to achieve the required clearance level for the uprated structure. Use of Transmission Line Arresters (TLAs) is an effective technique in controlling overvoltages and thereby, achieving the required clearance margin. In this paper, suitability of this technique in reducing the clearance margin is discussed. A case study on uprating an existing 275 kV overhead line to 400 kV is investigated here.
Keywords :
arresters; power overhead lines; power transmission protection; air clearance requirements; clearance level; line surge arresters; overhead line; transmission line arresters; uprated structure; voltage 275 kV; voltage 400 kV; voltage uprating; Arresters; Conductors; Insulation; Lightning; Poles and towers; Power system reliability; Power system transients; Power transmission lines; Surges; Voltage;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2009. CEIDP '09. IEEE Conference on
Conference_Location :
Virginia Beach, VA
Print_ISBN :
978-1-4244-4557-8
Electronic_ISBN :
0084-9162
DOI :
10.1109/CEIDP.2009.5377905