• DocumentCode
    3058557
  • Title

    Reverse-logic control of load tap changers in emergency voltage conditions

  • Author

    Otomega, Bogdan ; Sermanson, Vincent ; Van Cutsem, Thieny

  • Author_Institution
    Fac. of Power Eng., Bucharest Politechnica Univ., Romania
  • Volume
    1
  • fYear
    2003
  • fDate
    23-26 June 2003
  • Abstract
    This papers deals with the emergency control of load tap changers (LTCs) to face low transmission voltages or voltage instability situations. The proposed simple control logic consists in reverting the tap movements once the voltage at a monitored transmission bus falls below some threshold. A deadband on this voltage allows the system to settle down in between the normal and reverse logic modes. In order to control a large number of LTCs, the latter are divided into clusters, each with its own monitored voltage. The paper also considers the control of two levels of LTCs in cascade, where proper coordination is required between the two levels. The proposed scheme has been tested on a detailed EHV-HV-MV planning model of the Western region of the French transmission system operated by RTE. Long-term time responses to major disturbances are shown to illustrate the performance of the proposed scheme.
  • Keywords
    emergency power supply; on load tap changers; power system measurement; power transmission control; voltage control; French transmission system; emergency voltage conditions; load tap changers; low transmission voltages; reverse-logic control; transmission bus monitoring; voltage control; voltage instability situations; Control systems; Logic; Low voltage; Monitoring; Power engineering; Power generation; Power system restoration; System testing; Threshold voltage; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Tech Conference Proceedings, 2003 IEEE Bologna
  • Print_ISBN
    0-7803-7967-5
  • Type

    conf

  • DOI
    10.1109/PTC.2003.1304175
  • Filename
    1304175