DocumentCode
3061673
Title
Corona discharge activity on a string of glass cap-and-pin insulators under conditions of light wetting, light non-uniform contamination
Author
Bologna, F.F. ; Reynders, J.P. ; Britten, A.C.
Author_Institution
Eskom, Cleveland, South Africa
Volume
3
fYear
2003
fDate
23-26 June 2003
Abstract
The corona-like discharges on the top surfaces of lightly contaminated glass cap-and-pin insulators in a "V" configuration have been observed on an operational 400 kV line. Although it is postulated that such discharges may contribute to an insulator flashover, this is not the focus of this research. The objective of research described here is to replicate in the laboratory the corona-like discharges seen in the field. As a means of investigating this, field studies comprising the measurement of leakage current, insulator contamination and environmental parameters were done over a two-year period. The findings of this study were then used as the basis for controlled laboratory tests. The results and methods of this study have allowed replication of the top surface corona discharges seen in the field. The paper also discusses the role played by different wetting mechanisms associated with the observed types of discharge modes on lightly contaminated discs.
Keywords
contamination; corona; flashover; insulators; 400 kV; corona discharge activity; glass cap-and-pin insulators; insulator contamination; insulator flashover; leakage current measurement; light nonuniform contamination; light wetting; lightly contaminated discs; Corona; Current measurement; Flashover; Glass; Insulation; Laboratories; Leakage current; Pollution measurement; Surface contamination; Surface discharges;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN
0-7803-7967-5
Type
conf
DOI
10.1109/PTC.2003.1304409
Filename
1304409
Link To Document