DocumentCode :
3063124
Title :
Ground flash density and lightning exposure of power transmission lines
Author :
Diendorfer, D. ; Schulz, W.
Author_Institution :
Austrian Electrotechnical Assoc., OVE-ALDIS, Vienna, Austria
Volume :
3
fYear :
2003
fDate :
23-26 June 2003
Abstract :
Lightning is one of the major causes for outages in electric distribution and transmission networks. Data provided by a lightning location system in Austria allows detailed correlation of reported outages and the corresponding lightning discharges. Even within the small region of the Austrian territory the lightning flash exposure of HV transmission lines varies in a range from 0.6 to 2.6 km-2yr-1. A comparison of the actual observed lightning related line outages with calculated estimates based on the IEEE flash program show an underestimation of the outage rate by the flash program by a factor of about 2.
Keywords :
lightning; power transmission lines; 0.6 to 2.6 km; HV transmission lines; IEEE flash program; electric distribution; ground flash density; lightning discharges; lightning exposure; lightning location system; power transmission lines; transmission networks; Accuracy; Equations; Instruments; Lightning; Poles and towers; Power grids; Power transmission lines; Statistical analysis; Storms; Timing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN :
0-7803-7967-5
Type :
conf
DOI :
10.1109/PTC.2003.1304476
Filename :
1304476