DocumentCode
3064135
Title
Investigation into the effects of different antenna dimensions for UHF detection of partial discharges in power transformers
Author
Marangoni, F. ; Reynders, J.P. ; de Klerk, P.J.
Author_Institution
Sch. of Electr. & Information Eng., Witwatersrand Univ., Johannesburg, South Africa
Volume
3
fYear
2003
fDate
23-26 June 2003
Abstract
Detection of partial discharges (PDs) in power transformers can be seen as a means of anticipating imminent transformer failure and thus saving the transformer through planned maintenance. This work focuses on a ultra high frequency (UHF) technique for PD detection. A UHF antenna, capable of being fitted onto a standard DN5O transformer drain valve while maintaining an oil-tight seal, was designed for the purposes of this work. A surface discharge defect was created in the laboratory to study the effects that different antenna dimensions would have on the detected wideband UHF signal and determine an optimum frequency at which the defect can be detected.
Keywords
UHF antennas; partial discharges; power transformers; surface discharges; DN5O transformer drain valve; PD detection; UHF antenna; UHF detection; imminent transformer failure anticipation; optimum frequency; partial discharges; power transformers; surface discharge defect; ultra high frequency technique; Broadband antennas; Frequency; Laboratories; Oil insulation; Partial discharges; Power transformers; Seals; Surface discharges; UHF antennas; Valves;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech Conference Proceedings, 2003 IEEE Bologna
Print_ISBN
0-7803-7967-5
Type
conf
DOI
10.1109/PTC.2003.1304520
Filename
1304520
Link To Document