    A control method of active power filter in unsymmetrical voltage system

  • Author

    Komatsu, Yasuhiro ; Kawabata, Takao

  • Author_Institution
    Ritsumeikan Univ., Siga, Japan
  • Volume
    2
  • fYear
    1997
  • fDate
    26-29 May 1997
  • Firstpage
    839
  • Abstract
    In this paper, the authors propose a calculation method for compensating the current reference of an active power filter, where a nonlinear load exists in a three-phase three-wire asymmetrical voltage system. This new method has been named the extension pq method. The authors have experimented with the extension pq method and the pq method, using the same current controlled IPM inverter for both methods. The results of the experiments proved that in an asymmetrical voltage system, the source current was distorted in the case of the pq method, but was not distorted in the case of the extension pq method
  • Keywords
    active filters; compensation; harmonic distortion; load (electric); power convertors; power filters; power system harmonics; IPM inverter; active power filter; current reference compensation; diode bridge rectifier; extension pq method; nonlinear load; three-phase three-wire asymmetrical power system; Active filters; Control systems; Equations; IEC; Inverters; Nonlinear control systems; Nonlinear distortion; Proposals; Reactive power; Voltage control;