Title :
Parallel connection of several vacuum interrupters in a circuit-breaker pole
Author :
Pertsev, A.A. ; Belkin, G.S. ; Rylskaya, L.A.
Author_Institution :
All-Russian Electrotechnical Inslihtte (VEI), Krasnakazarmenaya str, 12.111250 Mosanu, Russia
fDate :
Sept. 27 2004-Oct. 1 2004
Abstract :
Experimental investigations of generator circuit-breaker prototype with parallel vacuum interrupters were carried out. The prototype braking and making capacity were high enough to use such circuit-breaker in generator circuit. The current dividing between vacuum interrupters allowed to achieve breaking current 80 kA and making current 150 kA peak. The authors found the limit of irregularity of current distribution during switching operation.
Keywords :
Circuit testing; Contacts; Current measurement; Electrical resistance measurement; Force measurement; Interrupters; Magnetic field measurement; Prototypes; Switching circuits; Voltage;
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV. XXIst International Symposium on
Conference_Location :
Yalta, Crimea
Print_ISBN :
0-7803-8461-X
DOI :
10.1109/DEIV.2004.1422614