DocumentCode :
3070771
Title :
Condition monitoring of vacuum circuit breakers using vibration analysis
Author :
YonPeng Meng ; Shenli Jia ; Mingzhe Rong
Author_Institution :
State Key Laboratory of Electrical Insulation for Power Equipment, Xi´an Jiaotong University, Xi´an, Shaanxi, China, 710049
Volume :
2
fYear :
2004
fDate :
Sept. 27 2004-Oct. 1 2004
Firstpage :
341
Lastpage :
344
Abstract :
Vibration analysis is a potential effective method for condition monitoring of circuit breakers (CBs). In this paper, a time-frequency method using an algorithm of wavelet packet is applied in the subsequent analysis for vibration signals. The vibration signal collected on the framework of vacuum circuit breaker by an acceleration sensor is decomposed into individual frequency bands and those bands that contain the main signal energy are extracted to form individual condition eigenvector. All eigenvectors derived from various conditions are used for Condition classification of CBs. Based on this monitoring method, asynchronous feature between three poles have been simulated in a 35kV vacuum circuit breaker and difference between vibration signals during close operation with no-load and that with short-circuit current is investigated, which verify the feasibility and accuracy of the vibration analysis in condition monitoring of vacuum circuit breakers.
Keywords :
Algorithm design and analysis; Circuit breakers; Condition monitoring; Frequency domain analysis; Signal analysis; Signal processing; Signal resolution; Vibrations; Wavelet analysis; Wavelet packets;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV. XXIst International Symposium on
Conference_Location :
Yalta, Crimea
ISSN :
1093-2941
Print_ISBN :
0-7803-8461-X
Type :
conf
DOI :
10.1109/DEIV.2004.1422616
Filename :
1422616
Link To Document :
بازگشت