DocumentCode :
3071089
Title :
Breaking capacity test of vacuum circuit breaker using synthetic test circuit with current zero forecast
Author :
Cai zhiyuan ; Ma Shaohua ; Dai Jun ; Wang Jinghui ; Wang Erzhi
Author_Institution :
College of Electrical Engineering, Shenyang University of Technology, Shenyang 11 0023, China. P. R
Volume :
2
fYear :
2004
fDate :
Sept. 27 2004-Oct. 1 2004
Firstpage :
387
Lastpage :
390
Abstract :
In order to test the breaking capacity of vacuum circuit breakers, it is needed to accurately control the synthetic test circuit so as to satisfy the test criterion. For the asymmetry breaking current, it is difficulty to ignite accurately the sphere gaps ahead before zero in an appointed time so as to turn on the arc prolonging current circuit and high voltage circuit. As a result, once asleep the synthetic testing would be unsuccessful. In this paper the synthetic test circuit with current zero forecast is presented. Based on the discussion of the digital signal processing technology, the control circuit has been set up, and the experiment shows a good agreement with the predictions.
Keywords :
Circuit breakers; Circuit testing; Current measurement; Current transformers; Frequency; RLC circuits; Switches; Switching circuits; Technology forecasting; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2004. Proceedings. ISDEIV. XXIst International Symposium on
Conference_Location :
Yalta, Crimea
ISSN :
1093-2941
Print_ISBN :
0-7803-8461-X
Type :
conf
DOI :
10.1109/DEIV.2004.1422628
Filename :
1422628
Link To Document :
بازگشت