DocumentCode
3073332
Title
Risk-Aware Attacks and Catastrophic Cascading Failures in U.S. Power Grid
Author
Wang, Wenkai ; Cai, Qiao ; Sun, Yan ; He, Haibo
Author_Institution
ECE Dept., Univ. of Rhode Island, Kingston, RI, USA
fYear
2011
fDate
5-9 Dec. 2011
Firstpage
1
Lastpage
6
Abstract
The power grid network is a complex network which is subjected to attacks and cascading failures. In this paper, we study the vulnerabilities of power grid in terms of cascading failures caused by node failures. Specifically, we define three metrics, the percentage-of-failure, Required Redundancy (RED), and Risk if Failure (RIF), to represent the critical level for each node. Based on these metrics, we can easily find the optimal victim nodes which attackers should choose to attack in order to cause cascading failure. From the defense point of view, these nodes are the weakest components of the power grid system and need more protection. With the results in this paper, we can be more aware of the risk level faced by the system if some nodes are taken down. Simulation results demonstrate the effectiveness of the proposed optimal victim nodes selection strategy.
Keywords
power grids; power system protection; catastrophic cascading failures; complex network; percentage of failure; power grid network; required redundancy; risk aware attacks; risk if failure; Load modeling; Measurement; Peer to peer computing; Power grids; Power system faults; Power system protection; Redundancy;
fLanguage
English
Publisher
ieee
Conference_Titel
Global Telecommunications Conference (GLOBECOM 2011), 2011 IEEE
Conference_Location
Houston, TX, USA
ISSN
1930-529X
Print_ISBN
978-1-4244-9266-4
Electronic_ISBN
1930-529X
Type
conf
DOI
10.1109/GLOCOM.2011.6133788
Filename
6133788
Link To Document