Study of transformer´s harmonic characteristic in DC magnetic bias
Author :
Mei, Guihua ; Liu, Yancun ; Guo, Mansheng
Author_Institution :
Guangdong Electr. Power Res. Inst., Guangzhou, China
fYear :
2008
fDate :
10-13 Dec. 2008
Firstpage :
1
Lastpage :
4
Abstract :
This paper selects one 500 kV mono-phase type transformer as the test object. Its no-load current includes dc component and even harmonics obviously in dc magnetic bias. With the increasing of the neutral dc current, the lower the harmonic order is, the more rapidly the harmonic current increases and the larger its percent on the basic-frequency component is. The dc component keeps 70% of the neutral dc current whether under undervoltage or overvoltage. When the neutral dc current is 4 A, dc magnetic bias comes into being in the transformer even under undervoltage. The research results can be used in the capacitor banks´ relay protection in 500 kV substations. The capacitor banks will be shut off once their 2nd harmonic current or the neutral dc current is over some setting value and time.
Keywords :
capacitor storage; harmonics; power transformers; DC magnetic bias; capacitor banks; harmonic characteristic; mono-phase type transformer; neutral dc current; relay protection; substations; voltage 500 kV; Capacitors; Circuit faults; Magnetic separation; Power harmonic filters; Power quality; Power system harmonics; Protective relaying; Substations; Testing; Voltage control; capacitor; dc magnetic bias; even; harmonic;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electricity Distribution, 2008. CICED 2008. China International Conference on
Conference_Location :
Guangzhou
Print_ISBN :
978-1-4244-3373-5
Electronic_ISBN :
978-1-4244-3372-8
Type :
conf
DOI :
10.1109/CICED.2008.5211707
Filename :
5211707
Link To Document :
بازگشت