• DocumentCode
    3081788
  • Title

    Study of transformer´s harmonic characteristic in DC magnetic bias

  • Author

    Mei, Guihua ; Liu, Yancun ; Guo, Mansheng

  • Author_Institution
    Guangdong Electr. Power Res. Inst., Guangzhou, China
  • fYear
    2008
  • fDate
    10-13 Dec. 2008
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper selects one 500 kV mono-phase type transformer as the test object. Its no-load current includes dc component and even harmonics obviously in dc magnetic bias. With the increasing of the neutral dc current, the lower the harmonic order is, the more rapidly the harmonic current increases and the larger its percent on the basic-frequency component is. The dc component keeps 70% of the neutral dc current whether under undervoltage or overvoltage. When the neutral dc current is 4 A, dc magnetic bias comes into being in the transformer even under undervoltage. The research results can be used in the capacitor banks´ relay protection in 500 kV substations. The capacitor banks will be shut off once their 2nd harmonic current or the neutral dc current is over some setting value and time.
  • Keywords
    capacitor storage; harmonics; power transformers; DC magnetic bias; capacitor banks; harmonic characteristic; mono-phase type transformer; neutral dc current; relay protection; substations; voltage 500 kV; Capacitors; Circuit faults; Magnetic separation; Power harmonic filters; Power quality; Power system harmonics; Protective relaying; Substations; Testing; Voltage control; capacitor; dc magnetic bias; even; harmonic;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution, 2008. CICED 2008. China International Conference on
  • Conference_Location
    Guangzhou
  • Print_ISBN
    978-1-4244-3373-5
  • Electronic_ISBN
    978-1-4244-3372-8
  • Type

    conf

  • DOI
    10.1109/CICED.2008.5211707
  • Filename
    5211707