DocumentCode
3083143
Title
Towards thermally-aware design of 3D MPSoCs with inter-tier cooling
Author
Sabry, Mohamed M. ; Sridhar, Arvind ; Atienza, David ; Temiz, Yuksel ; Leblebici, Yusuf ; Szczukiewicz, Sylwia ; Borhani, N. ; Thome, John R. ; Brunschwiler, Thomas ; Michel, Bruno
Author_Institution
Embedded Syst. Lab. (ESL), Ecole Polytech. Fed. de Lausanne (EPFL), Lausanne, Switzerland
fYear
2011
fDate
14-18 March 2011
Firstpage
1
Lastpage
6
Abstract
New tendencies envisage 3D Multi-Processor System-On-Chip (MPSoC) design as a promising solution to keep increasing the performance of the next-generation high-performance computing (HPC) systems. However, as the power density of HPC systems increases with the arrival of 3D MPSoCs, supplying electrical power to the computing equipment and constantly removing the generated heat is rapidly becoming the dominant cost in any HPC facility. Thus, both power and thermal/cooling implications play a major role in the design of new HPC systems, given the energy constraints in our society. Therefore, EPFL, IBM and ETHZ have been working within the CMOSAIC Nano-Tera.ch program project in the last three years on the development of a holistic thermally-aware design. This paper presents the exploration in CMOSAIC of novel cooling technologies, as well as suitable thermal modeling and system-level design methods, which are all necessary to develop 3D MPSoCs with inter-tier liquid cooling systems. As a result, we develop energy-efficient run-time thermal control strategies to achieve energy-efficient cooling mechanisms to compress almost 1 Tera nano-sized functional units into one cubic centimeter with a 10 to 100 fold higher connectivity than otherwise possible. The proposed thermally-aware design paradigm includes exploring the synergies of hardware-, software- and mechanical-based thermal control techniques as a fundamental step to design 3D MPSoCs for HPC systems. More precisely, we target the use of inter-tier coolants ranging from liquid water and two-phase refrigerants to novel engineered environmentally friendly nano-fluids, as well as using specifically designed micro-channel arrangements, in combination with the use of dynamic thermal management at system-level to tune the flow rate of the coolant in each micro-channel to achieve thermally-balanced 3D-ICs. Our management strategy prevents the system from surpassing the given threshold temperature while achieving up to 67%- reduction in cooling energy and up to 30% reduction in system-level energy in comparison to setting the flow rate at the maximum value to handle the worst-case temperature.
Keywords
cooling; multiprocessing systems; power aware computing; system-on-chip; 3D MPSoC; CMOSAIC Nano-Tera.ch program project; EPFL; ETHZ; HPC systems; IBM; dynamic thermal management; energy-efficient cooling mechanisms; energy-efficient run-time thermal control strategies; inter-tier liquid cooling systems; multi-processor system-on-chip; next-generation high-performance computing; thermally-aware design; Coolants; Heat transfer; Heating; Liquid cooling; Solid modeling; Three dimensional displays;
fLanguage
English
Publisher
ieee
Conference_Titel
Design, Automation & Test in Europe Conference & Exhibition (DATE), 2011
Conference_Location
Grenoble
ISSN
1530-1591
Print_ISBN
978-1-61284-208-0
Type
conf
DOI
10.1109/DATE.2011.5763237
Filename
5763237
Link To Document