Title :
Analysis of voltage tolerance of AC adjustable-speed drives for three-phase balanced and unbalanced sags
Author :
Bollen, M.H.J. ; Zhang, L.D.
Author_Institution :
Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Goteborg, Sweden
Abstract :
Adjustable-speed drives are the type of equipment most sensitive to voltage sags. This paper analyses the behavior of three-phase AC adjustable-speed drives during balanced and unbalanced sags. Emphasis is placed on the DC bus voltage and on the drop in speed, both assuming that the drive will not trip. By using a previously-introduced classification of three-phase unbalanced sags, voltage tolerance curves are obtained for AC adjustable-speed drives. The conclusion from the analysis is that voltage sags due to three-phase faults are a serious problem for adjustable-speed drives. However, single-phase and phase-to-phase faults, causing the majority of voltage sags, can be tolerated by adding a relatively small amount of DC bus capacitance
Keywords :
AC motor drives; power supply quality; power system faults; variable speed drives; AC adjustable-speed drives; DC bus capacitance; DC bus voltage; phase-to-phase faults; power quality; single-phase faults; speed drop; three-phase balanced sags; three-phase faults; three-phase unbalanced sags; voltage tolerance; Capacitance; Capacitors; Power engineering and energy; Power quality; Power system protection; Pulse width modulation; Rectifiers; Testing; Variable speed drives; Voltage fluctuations;
Conference_Titel :
Industrial & Commercial Power Systems Technical Conference, 1999 IEEE.
Conference_Location :
Sparks, NV
Print_ISBN :
0-7803-5593-8
DOI :
10.1109/ICPS.1999.787214