DocumentCode :
3091625
Title :
Experimental examination of wide-area current differential backup protection employing broadband communications and time transfer systems
Author :
Serizawa, Y. ; Imamura, H. ; Sugaya, N. ; Hori, M. ; Takeuchi, A. ; Inukai, M. ; Sugiura, H. ; Kagami, T.
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
2
fYear :
1999
fDate :
1999
Firstpage :
1070
Abstract :
Based on the authors´ previously proposed wide-area current differential backup protection utilizing broadband packet communications and time synchronous systems for achieving better selectivity, smaller outage areas and faster operation times than conventional distance backup protection, experimental microprocessor-based protection devices have been examined with respect to both telecommunication and protection functions. The experimental wide-area protection system consists of one central equipment (CE) unit and three terminal equipment (TE) units connected by a 155-Mbps ATM backbone network with a LAN interface and GPS time acquisition and features a simplified and effective method for expanding protection zones after primary or minimum-zone protection operation. In an AC power system simulator configuring a busbar and a power line, each TE at a circuit breaker location transmits sampled current data to the CE and receives a tripping command initiated by it, and operate satisfactorily in various states of power system and telecommunications
Keywords :
Global Positioning System; asynchronous transfer mode; broadband networks; local area networks; microcomputer applications; power system analysis computing; power system control; power system protection; synchronisation; telecontrol; 155 Mbit/s; ATM backbone network; GPS time acquisition; LAN interface; broadband communications; broadband packet communications; central equipment; computer simulation; microprocessor-based protection; protection zones; terminal equipment; time synchronous systems; time transfer systems; wide-area current differential backup protection; Asynchronous transfer mode; Circuit breakers; Global Positioning System; Power system protection; Power system relaying; Power system simulation; Power transmission lines; Protective relaying; Substation protection; Tellurium;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 1999. IEEE
Conference_Location :
Edmonton, Alta.
Print_ISBN :
0-7803-5569-5
Type :
conf
DOI :
10.1109/PESS.1999.787466
Filename :
787466
Link To Document :
بازگشت