Title :
Long-term test of the equipment for ±500 kV DC converter station
Author :
Tanaka, Y. ; Ono, T. ; Sampei, M. ; Obata, T. ; Tanabe, S. ; Tsuchie, E. ; Muraoka, T.
Author_Institution :
Kansai Electr. Power Co. Inc., Osaka, Japan
Abstract :
The paper describes the long-term test of prototypes of thyristor valves, DC GIS (gas insulated switchgear), converter transformers, smoothing reactors and a DC filter. These were developed for a HVDC system of ±500 kV, 2800 MW. To verify the long-term stable operation of the thyristor valves, 8 kV, 3500 A light triggered thyristors were assembled into a module of a commercial SVC (static VAr compensator) and tested for one year in operation. The other prototypes were subjected to an accelerated life test under ±625 kV DC at the test site. After one year, the equipment was brought back to the factory and tested to their performance limits to evaluate their remaining insulation capability. Successful tests confirmed that equipment based on the above prototypes can endure for a suitably long time in operation
Keywords :
HVDC power convertors; gas insulated switchgear; life testing; reactors (electric); static VAr compensators; substations; thyristor convertors; transformers; 2800 MW; 3500 A; 500 kV; 625 kV; 8 kV; DC GIS; DC filter; HVDC converter station; HVDC system; accelerated life test under; converter transformers; gas insulated switchgear; light triggered thyristors; long-term test; remaining insulation capability; smoothing reactors; static VAr compensator; thyristor valves; DC-DC power converters; Gas insulation; Geographic Information Systems; Life testing; Prototypes; Static VAr compensators; Switchgear; Switching converters; Thyristors; Valves;
Conference_Titel :
Power Engineering Society Summer Meeting, 1999. IEEE
Conference_Location :
Edmonton, Alta.
Print_ISBN :
0-7803-5569-5
DOI :
10.1109/PESS.1999.787479