A Novel Differential Protection Scheme for the Generator
Author
Jiajie, Zhu ; Nengling, Tai ; Chen, Chen
Author_Institution
Dept. of Power Electr. Eng., Shanghai Jiaotong Univ., Shanghai
fYear
2007
fDate
24-28 June 2007
Firstpage
1
Lastpage
6
Abstract
This paper presents a new scheme to distinguish the internal fault or the external fault based on phaselet algorithm. For the generator ratio restraint differential protection, the restraint current is decreased owing to CT saturation caused by the external fault, which always results in the maloperation. In order to enhance the operating characteristic of the protection, generator differential protection will select different restraint currents according to the different fault current characteristics. According to that, the method for choosing the corresponding restraint currents is then introduced. The simulation results show that the scheme can effectively prevent the generator differential protection from maloperation caused by CT saturation, and availably enhance the sensitivity of the differential protection during the internal fault.
Keywords
electric generators; fault currents; fault diagnosis; machine protection; different fault current characteristics; external fault; generator ratio restraint differential protection; internal fault; phaselet algorithm; Character generation; Circuit faults; Difference equations; Fault currents; Fault detection; Impedance; Power generation; Protection; Protective relaying; Relays; differential protection; generator; phaselet; restraint current; saturation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2007. IEEE
Conference_Location
Tampa, FL
ISSN
1932-5517
Print_ISBN
1-4244-1296-X
Electronic_ISBN
1932-5517
Type
conf
DOI
10.1109/PES.2007.385535
Filename
4275417
Link To Document