Abstract
Based on the analysis of the relationship between the terminal voltages and the reactive power of a generator, the shortcomings of the available scheme to protect generators in parallel from overvoltage have been pointed out, and a novel overvoltage protection scheme is put forward. For machines connected directly to busbars, especially for powerformers, a novel type of high voltage generators, this protection makes it possible to identify which machine that is the source of the overvoltage by virtue of the variety of reactive power. Use a compensated voltage factor to modify the operating time of the protection and trip the generator which has the most vital impact on the overvoltage of the busbar first. The effectiveness of this scheme is validated with the EMTDC simulation results.
Keywords
busbars; electric generators; overvoltage protection; reactive power; EMTDC simulation; busbar; generator reactive power; high voltage generators; overvoltage protection; powerformer; reactive power; voltage factor compensation; Analytical models; EMTDC; Electronic mail; IEEE members; Power generation; Power system modeling; Power system protection; Power transmission lines; Reactive power; Voltage control; EMTDC; Powerformer; overvoltage protection; reactive power;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2007. IEEE
Conference_Location
Tampa, FL
ISSN
1932-5517
Print_ISBN
1-4244-1296-X
Electronic_ISBN
1932-5517
Type
conf
DOI
10.1109/PES.2007.385776
Filename
4275542
Link To Document