Title :
Screening Study of Sudden Power Change on Generators due to Transmission Line Re-closing
Author :
Hsu, Shih-Min ; Horton, Randy
Author_Institution :
Transm. Planning, Southern Co. Transm., Birmingham, AL
Abstract :
It has been known for some time that generators should avoid having a sudden power change greater than 0.5 pu during nearby transmission line switching operations, especially the re-closing operations. This paper suggests that a study on transmission line re-closing should be performed at the initial interconnection study. This paper discusses the potential problem and gives some possible solutions. One solution is ramping down generation to reduce the angle across the breaker before re-closing the breaker. A promising novel solution, a special switching scheme, is presented in the paper. By implementing this scheme, the possibility of ramping down generation might be eliminated, or, at least, the amount of ramping down could be reduced.
Keywords :
circuit breakers; power generation protection; power system interconnection; power transmission lines; circuit breaker; generator protection; initial interconnection study; transmission line reclosing; transmission line switching operations; Circuit breakers; Distributed parameter circuits; Joining processes; Mesh generation; Power generation; Power system transients; Power transmission lines; Protective relaying; Substations; Turbines; Generator protection; automatic re-closing; dynamic simulation; line loading; synch-check relay;