DocumentCode
3103212
Title
Measurement placement algorithms for state estimation when the number of phasor measurements by each PMU is limited
Author
Hurtgen, Michael ; Praks, Pavel ; Maun, Jean-Claude ; Zajac, Petr
Author_Institution
Univ. Libre de Bruxelles, Brussels
fYear
2008
fDate
1-4 Sept. 2008
Firstpage
1
Lastpage
5
Abstract
It is essential for Energy Management Systems (EMS) applications and control centre technologies that the measurements allow monitoring of the power system. An important tool for the EMS is state estimation which makes it possible to estimate the state variables of the power system based on these measurements. The measurements should allow observability of the power system which means they can be used to describe the system. The objective of the paper is to develop an algorithm for placement of PMUs in order to make the system observable. The novelty is that a limit on the number of measurements each PMU can make is introduced. The number of PMUs needed to make the network observable will therefore depend on the maximum number of measurements each PMU can make. The algorithm is tested on three IEEE test networks.
Keywords
energy management systems; phase measurement; power system measurement; energy management systems; measurement placement algorithms; phasor measurements; power system control; power system monitoring; power system operation; Control systems; Energy management; Energy measurement; Medical services; Monitoring; Phasor measurement units; Power measurement; Power system measurements; State estimation; Testing; Power System Operation and Control; State estimation; observability; phasor measurement unit (PMU);
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2008. UPEC 2008. 43rd International
Conference_Location
Padova
Print_ISBN
978-1-4244-3294-3
Electronic_ISBN
978-88-89884-09-6
Type
conf
DOI
10.1109/UPEC.2008.4651437
Filename
4651437
Link To Document