Abstract :
This paper describes field trials of voltage reduction on nine distribution circuits. The median CVR factor was 0.6 on these circuits. Results were normalized using measurements from nearby comparable circuits. Advanced metering infrastructure data on some circuits allowed comparison by customer type. On one circuit, commercial customers had lower CVR factors than residential customers. For residential customers, CVR factors were lower for customers with higher winter loads.
Keywords :
power distribution; commercial customers; distributions circuits; median CVR factor; residential customers; voltage reduction field trials; Integrated circuit modeling; Load modeling; Reactive power; Substations; Temperature measurement; Voltage control; Voltage measurement; Power distribution; conservation voltage reduction; efficiency;