• DocumentCode
    3104116
  • Title

    Sustained response of unbalanced electric system represented through three-phase two-port networks

  • Author

    Zevallos, M.E. ; Tavares, M.C.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Fed. Inst. of Bahia (IFBA), Salvador, Brazil
  • fYear
    2012
  • fDate
    7-10 May 2012
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This paper proposes the use of three-phase two ports elements to obtain the sustained response of unbalanced electric power system. Representations of three-phase two-ports networks for various types of elements of the electrical power system are described. The methodology is applied to identify the optimum neutral reactor that minimizes the secondary arc current in a transmission system, thus enabling the single-phase auto-reclosing switching implementation.
  • Keywords
    arcs (electric); power transmission; reactors (electric); optimum neutral reactor; secondary arc current; single-phase auto-reclosing switching; three-phase two-port networks; transmission system; unbalanced electric power system; Admittance; Circuit breakers; Impedance; Inductors; Shunt (electrical); Transmission line matrix methods; Cascade Association; Sustained Response; Three-phase Two-port Network; Unbalanced System;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition (T&D), 2012 IEEE PES
  • Conference_Location
    Orlando, FL
  • ISSN
    2160-8555
  • Print_ISBN
    978-1-4673-1934-8
  • Electronic_ISBN
    2160-8555
  • Type

    conf

  • DOI
    10.1109/TDC.2012.6281563
  • Filename
    6281563