Title :
Locating inter-disc faults in transformer winding using frequency response analysis
Author :
Yousof, M.F.M. ; Ekanayake, Chandima ; Saha, Tapan K.
Author_Institution :
Sch. of Inf. Technol. & Electr. Eng., Univ. of Queensland, St. Lucia, QLD, Australia
fDate :
Sept. 29 2013-Oct. 3 2013
Abstract :
Frequency response analysis (FRA) is a technique for evaluating the mechanical integrity of power transformers. This paper proposes a methodology to locate inter-disc fault in a transformer winding through FRA measurements. A core-type three phase transformer is used for simulating faults on several locations along the interleaved winding, from top to bottom end. Correlation coefficient, vector fitting and Nyquist plot are employed to assist in the analysis. By drawing the transfer function of the winding response on Nyquist plot, key information is extracted and two equations are developed to locate the fault.
Keywords :
Nyquist criterion; cores; fault location; frequency response; power transformers; transformer windings; Correlation coefficient; FRA measurements; Nyquist plot; core-type three phase transformer; fault simulation; frequency response analysis; inter-disc faults location; interleaved winding; mechanical integrity; power transformer; power transformers; transfer function; transformer winding; vector fitting; winding response; Correlation; Impedance; Lead; Windings; frequency response analysis; transfer function; transformer; winding;
Conference_Titel :
Power Engineering Conference (AUPEC), 2013 Australasian Universities
Conference_Location :
Hobart, TAS
DOI :
10.1109/AUPEC.2013.6725454