Abstract :
Sub-Synchronous Interaction (SSI), in regard to wind power generation, can result from the interaction of wind power generation control systems and series capacitors. SSI occurred in South Texas in 2009, when wind generation was isolated behind a series capacitor. Three measures should be pursued to avoid SSI. Wind generation should implement control system enhancements, Transmission Service Providers (TSP) should evaluate the cost effectiveness of series compensation SSI mitigation, and both generation and transmission should implement protection systems.
Keywords :
compensation; power capacitors; power generation control; power generation protection; power transmission protection; wind power plants; SSI avoidance; SSI mitigation; South Texas; TSP; control system enhancements; generation system protection; series capacitors; series compensation; subsynchronous interaction; transmission operator; transmission service providers; transmission system protection; wind power generation control systems; Capacitors; EMTP; Generators; Integrated circuit interconnections; Power transmission lines; Wind farms; Wind power generation; Electro-Magnetic Transient Program (EMTP) sub-synchronous interaction (SSI); bypass filter; thyristor switched series capacitors (TCSC); wind power generation;