DocumentCode :
3111988
Title :
Cascaded multilevel inverter based shunt active power filter in four-wire distribution system
Author :
Abdalla, Izzeldin Idris ; Rao, K. S Rama ; Perumal, N.
Author_Institution :
Dept. of Electr. & Electron. Eng., Univ. Teknol. PETRONAS, Tronoh, Malaysia
fYear :
2011
fDate :
19-20 Sept. 2011
Firstpage :
1
Lastpage :
6
Abstract :
This paper presents a compensating system for the harmonics and the reactive power in a four-wire distribution system, using five-level cascaded inverter based shunt active power filter (SAPF). The distribution network which supplies mixed nonlinear loads and employing SAPF is simulated by MATLAB/SIMULINK software. The Simulation results indicate that with the proposed control method, the SAPF is capable of compensating the source current harmonics and the reactive power. Simultaneously the THD is minimized and the neutral current is maintained close to zero.
Keywords :
active filters; compensation; distribution networks; harmonic distortion; invertors; power harmonic filters; reactive power; Matlab-Simulink software; THD; cascaded multilevel inverter based shunt active power filter; compensating system; distribution network; five-level cascaded inverter; four-wire distribution system; neutral current; reactive power; source current harmonic compensation; total harmonic distortion; Active filters; Harmonic analysis; Inverters; Mathematical model; Power harmonic filters; Reactive power; Harmonics and reactive power compensation; multilevel voltage source inverter; shunt active power filter; total harmonics distortion;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
National Postgraduate Conference (NPC), 2011
Conference_Location :
Kuala Lumpur
Print_ISBN :
978-1-4577-1882-3
Type :
conf
DOI :
10.1109/NatPC.2011.6136339