DocumentCode
3113502
Title
Experimental study on DC biasing impact on transformer’s vibration and sound
Author
Ma, Hongbin ; He, Jinliang ; Zhang, Bo ; Zeng, Rong ; Chen, Shuiming ; Cao, Lin
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing
fYear
2008
fDate
18-22 Aug. 2008
Firstpage
1
Lastpage
4
Abstract
DC biasing current through the neutral point of ac power transformer would lead the power transformer to generate more vibration and sound, this will do harm on power transformerspsila core pieces or windings and finally will threaten the safe operation of the transformers. This paper described the principle of DC biasing, designed a new DC biasing experiment to analyze how the experimental transformerpsilas vibration and sound change along with the value of DC biasing current or windings voltage and finally some curves were given in order to show the direct connection between vibration peak value, sound pressure and DC current.
Keywords
power transformers; vibrations; DC biasing; DC current; ac power transformer; sound pressure; transformer safe operation; transformer vibration; vibration peak value; windings voltage; Earth; HVDC transmission; Magnetic cores; Magnetic flux; Magnetostriction; Power grids; Power transformers; Testing; Transformer cores; Vibration measurement; DC biasing; power transformer; sound pressure; vibration;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 2008. EMC 2008. IEEE International Symposium on
Conference_Location
Detroit, MI
Print_ISBN
978-1-4244-1699-8
Electronic_ISBN
978-1-4244-1698-1
Type
conf
DOI
10.1109/ISEMC.2008.4652028
Filename
4652028
Link To Document