• DocumentCode
    3124330
  • Title

    Behavior of doubly-fed induction generator during symmetrical voltage dips — Experimental results

  • Author

    Mendes, Victor F. ; de Sousa, C.V. ; Silva, Selênio R. ; Rabelo, Balduino ; Krauss, Sebastian ; Hofmann, Wilfried

  • Author_Institution
    Dept. of Electr. Eng., Fed. Univ. of Minas Gerais, Belo Horizonte, Brazil
  • fYear
    2010
  • fDate
    4-7 July 2010
  • Firstpage
    2345
  • Lastpage
    2350
  • Abstract
    Wind energy conversion systems using the doubly-fed induction generator (DFIG) are the most commercialized topology worldwide, because this technology uses converters dimensioned for ±30% of the system rated power, thus reducing the equipment cost. The direct connection of the DFIG stator to the electrical system increases its sensitivity to grid disturbances. In this context, this paper analyzes the DFIG behavior during balanced voltage sags using the machine classical model for the theoretical development and analyzing experimental results of a 2.2 kW test bench equipped with a crowbar device. The obtained results are useful in the development of strategies to improve the DFIG supportability during grid disturbances.
  • Keywords
    asynchronous generators; power supply quality; wind power plants; DFIG stator; doubly fed induction generator; grid disturbance; power 2.2 kW; symmetrical voltage dips; wind energy conversion; Converters; Couplings; Generators; Rotors; Stators; Voltage control; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics (ISIE), 2010 IEEE International Symposium on
  • Conference_Location
    Bari
  • Print_ISBN
    978-1-4244-6390-9
  • Type

    conf

  • DOI
    10.1109/ISIE.2010.5637739
  • Filename
    5637739