    A transient fault detection technique with varying fault detection window of earth modes in unearthed MV systems

  • Author

    Abdel-Fattah, Mohamed F. ; Lehtonen, Matti

  • Author_Institution
    Dept. of Electr. Eng., Helsinki Univ. of Technol. (TKK), Espoo
  • fYear
    2008
  • fDate
    27-29 Aug. 2008
  • Firstpage
    181
  • Lastpage
    186
  • Abstract
    This paper presents a transient fault detection technique in unearthed medium voltage systems. The system is simulated by ATP/EMTP program. A suitable fault detection window is introduced. The window width is the most sensitive part in the transient period. It is varying according to fault characteristics. The average impedance of the earth mode is calculated from voltage and current earth modes in the window. Based on the amplitude of the impedance, the feeder is confirmed to be faulted or not. The setting of detection is proposed from the simulation results that cover different fault inception angles and fault resistances.
  • Keywords
    earthing; fault diagnosis; transient analysis; ATP-EMTP program; average impedance; current earth mode; earth mode; fault detection window varying; fault inception angle; fault resistance; transient fault detection technique; unearthed MV system; voltage earth mode; Circuit faults; Earth; Electrical fault detection; Fault detection; Frequency; Impedance; Power system protection; Power system simulation; Power system transients; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Quality and Supply Reliability Conference, 2008. PQ 2008
  • Conference_Location
    Parnu
  • Print_ISBN
    978-1-4244-2500-6
  • Electronic_ISBN
    978-1-4244-2501-3
  • Type

    conf

  • DOI
    10.1109/PQ.2008.4653758
  • Filename
    4653758