• DocumentCode
    3135436
  • Title

    Smart protection in Dutch Medium Voltage distributed generation systems

  • Author

    Xyngi, Ioanna ; Popov, Marjan

  • Author_Institution
    Fac. of Electr. Eng., Math. & Inf., Delft Univ. of Technol., Delft, Netherlands
  • fYear
    2010
  • fDate
    11-13 Oct. 2010
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    The paper investigates the impact of distributed generators integration in Dutch Medium Voltage grids. Typical protection problems are described and analyzed. The current applied time-graded overcurrent protection scheme is evaluated and its shortcomings are highlighted. A new software algorithm for coordinating relays in any arbitrary network is proposed. The real hardware implementation of the protection scheme that makes use of an advanced sensor and microprocessor technology, and a communication infrastructure is explained in details. Simulation results reveal significant improvements in the protection speed performance and the DG during-fault availability.
  • Keywords
    microprocessor chips; overcurrent protection; power distribution protection; power engineering computing; power generation protection; sensors; smart power grids; DG during-fault availability; Dutch medium voltage grid; distributed generation system; distributed generator; microprocessor; sensor; smart protection; software algorithm; time-graded overcurrent protection; Circuit faults; Fault location; Generators; Integrated circuit modeling; Mathematical model; Relays; Substations; IEC 61850; SASensor; distributed generators; distribution system; protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES
  • Conference_Location
    Gothenburg
  • Print_ISBN
    978-1-4244-8508-6
  • Electronic_ISBN
    978-1-4244-8509-3
  • Type

    conf

  • DOI
    10.1109/ISGTEUROPE.2010.5638982
  • Filename
    5638982