DocumentCode :
3135617
Title :
Distribution transformer load allocation from substation measurements and load patterns
Author :
Carmona, C. ; Romero-Ramos, E. ; Riquelme, J. ; Gómez-Expósito, A.
Author_Institution :
Dept. of Electr. Eng., Univ. of Sevilla, Sevilla, Spain
fYear :
2010
fDate :
11-13 Oct. 2010
Firstpage :
1
Lastpage :
8
Abstract :
This paper proposes a new method to split the total load measured at the head of a distribution feeder into a set of individual loads served by those transformers connected to the feeder. For this purpose, a least-squares estimator is formulated, trying to reconcile hourly substation measurements of aggregated feeder load with historical 24-hour records of typical end-use demand profiles. The results of different tests are included to validate the proposed technique and illustrate its potential benefits and limitations.
Keywords :
demand side management; least squares approximations; load distribution; power distribution; power system measurement; power transformers; substations; distribution feeder; distribution transformer load allocation; end-use demand profile; least-squares estimator; load pattern; substation measurement; Current measurement; Indexes; Optimization; Reactive power; Resource management; Substations; Voltage measurement; Load allocation; daily load patterns; distribution systems; least squares; load estimation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES
Conference_Location :
Gothenburg
Print_ISBN :
978-1-4244-8508-6
Electronic_ISBN :
978-1-4244-8509-3
Type :
conf
DOI :
10.1109/ISGTEUROPE.2010.5638995
Filename :
5638995
Link To Document :