DocumentCode
3135796
Title
A voltage sag study in a large industrial distribution system
Author
Bollen, M.H.J. ; Yalçinkaya, G. ; Pellis, J. ; Qader, M.R.
Author_Institution
Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
Volume
4
fYear
1996
fDate
6-10 Oct 1996
Firstpage
2372
Abstract
The method of fault positions has been used to study the post-fault voltage sags in the supply to a large chemical industry plant. The main concern is faults in the on-site distribution systems. The during-fault and post-fault voltages have been simulated by using the PSCAD/EMTDC package. A comparison with a measured sag has been made, showing good agreement. The simulation results taught us that post-fault voltage sags mainly occur during faults in the MV networks. Strengthening the supply, or reducing the (post-fault) motor load are needed to solve this
Keywords
chemical industry; distribution networks; fault location; industrial plants; industrial power systems; power system analysis computing; MV networks; PSCAD/EMTDC package; chemical industry plant; during-fault voltages; industrial distribution system; measured voltage sag; motor load reduction; post-fault voltage sags; supply strengthening; voltage sag; voltage simulation; Chemical industry; Chemical technology; Costs; Induction motors; Low voltage; Power quality; Power system stability; Redundancy; Shape; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Conference, 1996. Thirty-First IAS Annual Meeting, IAS '96., Conference Record of the 1996 IEEE
Conference_Location
San Diego, CA
ISSN
0197-2618
Print_ISBN
0-7803-3544-9
Type
conf
DOI
10.1109/IAS.1996.563903
Filename
563903
Link To Document