• DocumentCode
    3135796
  • Title

    A voltage sag study in a large industrial distribution system

  • Author

    Bollen, M.H.J. ; Yalçinkaya, G. ; Pellis, J. ; Qader, M.R.

  • Author_Institution
    Centre for Electr. Energy, Univ. of Manchester Inst. of Sci. & Technol., UK
  • Volume
    4
  • fYear
    1996
  • fDate
    6-10 Oct 1996
  • Firstpage
    2372
  • Abstract
    The method of fault positions has been used to study the post-fault voltage sags in the supply to a large chemical industry plant. The main concern is faults in the on-site distribution systems. The during-fault and post-fault voltages have been simulated by using the PSCAD/EMTDC package. A comparison with a measured sag has been made, showing good agreement. The simulation results taught us that post-fault voltage sags mainly occur during faults in the MV networks. Strengthening the supply, or reducing the (post-fault) motor load are needed to solve this
  • Keywords
    chemical industry; distribution networks; fault location; industrial plants; industrial power systems; power system analysis computing; MV networks; PSCAD/EMTDC package; chemical industry plant; during-fault voltages; industrial distribution system; measured voltage sag; motor load reduction; post-fault voltage sags; supply strengthening; voltage sag; voltage simulation; Chemical industry; Chemical technology; Costs; Induction motors; Low voltage; Power quality; Power system stability; Redundancy; Shape; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 1996. Thirty-First IAS Annual Meeting, IAS '96., Conference Record of the 1996 IEEE
  • Conference_Location
    San Diego, CA
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-3544-9
  • Type

    conf

  • DOI
    10.1109/IAS.1996.563903
  • Filename
    563903