• DocumentCode
    3142173
  • Title

    Chaos and Ferroresonance

  • Author

    Li, Huawei ; Fan, Yu ; Shi, Rong

  • Author_Institution
    Sch. of Electr. Eng., Beijing Jiaotong Univ.
  • fYear
    2006
  • fDate
    38838
  • Firstpage
    494
  • Lastpage
    497
  • Abstract
    The impact of capacitance on magnitudes and frequencies of ferroresonance overvoltage is studied for a 35 kV distribution network. The research is conducted on a general-purpose electro-magnetic transient program (EMTP). We show that circuits alternate between ferroresonance and non-resonance when capacitance increases. Therefore, it is not an effective method to expire ferroresonance through adding capacitors at buses. We also proof that chaos is one of the characteristics of ferroresonance
  • Keywords
    EMTP; capacitance; chaos; ferroresonant circuits; overvoltage; power distribution faults; 35 kV; EMTP; capacitance; chaos; distribution network; electro-magnetic transient program; ferroresonance overvoltage; Capacitance; Chaos; Circuits; EMTP; Ferroresonance; Inductance; Power system simulation; Power system transients; Voltage control; Voltage transformers; Chaos; EMTP; Ferroresonance; Restriction methods;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Computer Engineering, 2006. CCECE '06. Canadian Conference on
  • Conference_Location
    Ottawa, Ont.
  • Print_ISBN
    1-4244-0038-4
  • Electronic_ISBN
    1-4244-0038-4
  • Type

    conf

  • DOI
    10.1109/CCECE.2006.277616
  • Filename
    4054951