Abstract
The impact of capacitance on magnitudes and frequencies of ferroresonance overvoltage is studied for a 35 kV distribution network. The research is conducted on a general-purpose electro-magnetic transient program (EMTP). We show that circuits alternate between ferroresonance and non-resonance when capacitance increases. Therefore, it is not an effective method to expire ferroresonance through adding capacitors at buses. We also proof that chaos is one of the characteristics of ferroresonance
Keywords
EMTP; capacitance; chaos; ferroresonant circuits; overvoltage; power distribution faults; 35 kV; EMTP; capacitance; chaos; distribution network; electro-magnetic transient program; ferroresonance overvoltage; Capacitance; Chaos; Circuits; EMTP; Ferroresonance; Inductance; Power system simulation; Power system transients; Voltage control; Voltage transformers; Chaos; EMTP; Ferroresonance; Restriction methods;