DocumentCode :
3147478
Title :
Analysis of the potential distribution in a relay cell generated by a direct lightning strike in a 500 kV substation
Author :
Maolin, Wu ; Xiang, Cui ; Zhongyuan, Zhang
Author_Institution :
North China Electr. Power Univ., Hebei, China
fYear :
2002
fDate :
21-24 May 2002
Firstpage :
198
Lastpage :
201
Abstract :
The protection and controlling devices have been moved into the relay cell in the switchyard from the controlling building in some newly-built 500 kV substations in China. The transient grounding potential rise will be caused in a relay cell by a direct lightning strike in a 500 kV substation and be harmful to the secondary devices. Therefore, it is very important to predict the transient potential distribution in the relay cell. The authors calculated and analyzed the transient grounding potential distribution, found the appropriate mode of the inner grounding grid in the relay cell. Thus, the electromagnetic interference that the protection and controlling devices will suffer from the transient grounding potential rise in the relay cell can be reduced greatly.
Keywords :
earth electrodes; lightning protection; relay protection; substation automation; substation protection; China; controlling device; direct lightning strike; inner grounding grid; potential distribution; protection device; relay cell; secondary devices; transient grounding potential distribution; transient grounding potential rise; transient potential distribution; Electromagnetic transients; Frequency; Grounding; Lighting control; Lightning; Protective relaying; Relays; Steel; Substation protection; Transient analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility, 2002 3rd International Symposium on
Print_ISBN :
0-7803-7277-8
Type :
conf
DOI :
10.1109/ELMAGC.2002.1177402
Filename :
1177402
Link To Document :
بازگشت