DocumentCode
3148320
Title
Measurement and analysis of EMI at main control room in Uljin nuclear power plant
Author
Song, Tae-Seung ; Cho, Won-Seo ; Goo, Cheol-Soo
Author_Institution
EMC Team, Korea Testing Lab., Seoul, South Korea
fYear
2002
fDate
21-24 May 2002
Firstpage
374
Lastpage
377
Abstract
In this paper, conducted and radiated noise at the power and enclosure ports of the plant control system and the core protection calculator installed at main control room in Uljin nuclear power plant were measured and analyzed. The measurement was performed continuously over a period of two months in which the power output was elevated progressively in phases from reactor power of 0% to 100%. The measurement consisted of performing conducted emissions in the frequency range of 30 Hz to 30 MHz, and radiated emissions in the frequency range of 30 Hz to 7 GHz. The measured values and profiles for conducted and radiated emissions were similar to those of nuclear plants gathered in United States. The conducted and radiated limits, which are applicable to Korean standard, using the recursive least square analysis technique were derived from measured data. The limits obtained were compared with those of United States Nuclear Regulatory Commission (USNRC) and Electric Power Research Institute (EPRI).
Keywords
electromagnetic compatibility; electromagnetic interference; nuclear power stations; power station control; 30 Hz to 30 MHz; 30 Hz to 7 GHz; EMI analysis; EMI measurement; conducted emissions; conducted noise; control room EMI studies; nuclear power plant; radiated emissions; radiated noise; Control systems; Electromagnetic interference; Frequency; Noise measurement; Nuclear measurements; Performance evaluation; Phase measurement; Power generation; Power measurement; Power system protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 2002 3rd International Symposium on
Print_ISBN
0-7803-7277-8
Type
conf
DOI
10.1109/ELMAGC.2002.1177448
Filename
1177448
Link To Document