DocumentCode :
3148742
Title :
Studying effect of location and resistance of inter-turn faults on fault current in power transformers
Author :
Zhalefar, Farzad ; Sanaye-Pasand, M.
Author_Institution :
Univ. of Tehran, Tehran
fYear :
2007
fDate :
4-6 Sept. 2007
Firstpage :
138
Lastpage :
142
Abstract :
Inter-turn (turn-to-turn) fault is one of the most important failures which could occur in power transformers. This phenomenon could seriously reduce the useful life length of transformers. Meanwhile, transformer protection schemes such as differential relays are not able to detect this kind of fault. This type of fault should be studied carefully to determine its features and characteristics. In this paper the effect of fault location and fault resistance on the amplitude of fault current is studied. It is found that change of fault location along the winding has considerable effect on fault current amplitude. It would also be shown that, even small fault resistance could have major effect on fault current amplitude. In this paper, a real 240/11 kV, 27 MVA transformer is used for simulation studies.
Keywords :
fault location; fault simulation; power transformer protection; TOK software; fault current; fault resistance; inter-turn fault location; power transformer protection; transformer life length; voltage 11 kV; voltage 240 kV; Circuit faults; Fault currents; Fault detection; Fault location; Power system simulation; Power transformer insulation; Power transformers; Protection; Protective relaying; Surges; Fault resistance; Inter-turn fault; Power transformers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference, 2007. UPEC 2007. 42nd International
Conference_Location :
Brighton
Print_ISBN :
978-1-905593-36-1
Electronic_ISBN :
978-1-905593-34-7
Type :
conf
DOI :
10.1109/UPEC.2007.4468934