Performance comparison of current differential protection scheme based on symmetrical components
Author
Zhang, Ning ; Dong, Xinzhou ; Bo, Zhiqian ; Klimek, Andrew
Author_Institution
Tsinghua Univ., Beijing
fYear
2007
fDate
4-6 Sept. 2007
Firstpage
305
Lastpage
309
Abstract
This paper presents the extended study on current differential protection schemes based on symmetrical components. The principles of the protection schemes are analyzed firstly. Their performances are evaluated on a typical 500 kV power transmission line system model using EMTP. Extensive simulation studies are presented under various system and fault conditions, such as variations in system load currents, fault resistances, fault location and fault types. Comprehensive comparison based on theoretic analysis and extensive simulation shows that negative-sequence current differential protection provides the best performance.
Keywords
EMTP; fault currents; fault location; power transmission faults; power transmission lines; power transmission protection; EMTP; fault location; fault resistances; negative-sequence current differential protection scheme; power transmission line system model; symmetrical components; system load currents; voltage 500 kV; Performance analysis; Power system analysis computing; Power system faults; Power system protection; Power system relaying; Power system simulation; Power system transients; Power transmission lines; Protective relaying; Transmission line theory; Current Differential Protection; Symmetrical Components; Transmission Line Protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Universities Power Engineering Conference, 2007. UPEC 2007. 42nd International
Conference_Location
Brighton
Print_ISBN
978-1-905593-36-1
Electronic_ISBN
978-1-905593-34-7
Type
conf
DOI
10.1109/UPEC.2007.4468965
Filename
4468965
Link To Document