DocumentCode :
3151103
Title :
Life management of GIS based on deterioration diagnosis of aged GIS
Author :
Kawakita, K. ; Ota, H. ; Simokawa, M. ; Kuwabara, Y.
Author_Institution :
Chubu Electr. Power Co., Inc, Japan
Volume :
2
fYear :
2002
fDate :
6-10 Oct. 2002
Firstpage :
802
Abstract :
Gas Insulated Switchgear (GIS) is composed of several components such as circuit breaker, disconnecting switch, lightning arrester and so on. Although life-time of each component is evaluated, however there are few examinations on the whole of GIS. This time, we have overhauled and investigated all the components of the 77 kV outdoor type GIS at Moriyama Substation and Tsukioka-cho Substation of Chubu Electric Power Co Inc. which have been in service for 31 years and 30 years respectively. Then, we analyzed the deterioration progress and its process of GIS from the results of overhaul together with our technical experiences. Therefore, we could obtain very useful deterioration diagnostic data and identify the parts affecting the GIS lifetime. Based on these results, we have summarized external diagnostic and repair technologies, which are effective for GIS life management, and items to be newly reflected to design.
Keywords :
ageing; electric breakdown; fault diagnosis; gas insulated switchgear; insulation testing; maintenance engineering; switchgear testing; 30 year; 31 year; 77 kV; GIS life management; Japan; aged GIS; circuit breaker; deterioration diagnosis; diagnostic data; disconnecting switch; gas insulated switchgear; lightning arrester; repair technologies; Aging; Arresters; Circuit breakers; Gas insulation; Geographic Information Systems; Lightning; Substations; Switches; Switchgear; Switching circuits;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
Type :
conf
DOI :
10.1109/TDC.2002.1177578
Filename :
1177578
Link To Document :
بازگشت