Abstract :
This work elucidates how the authors detected a discoordination case involving overcurrent relays of a feeder and a electric energy substation transformer of AES Sul-Distribuidora Gaucha de Energia concession´s area, originating on the disregarding, on the protection adjust period, of the different load levels of distribution feeders and total current from the substation transformer. If the relays didn´t include an oscillographics option on substation digital protection, this problem probably would not be recognized. Also, the providences to this problem of bad coordination in the company are presented.
Keywords :
overcurrent protection; power system measurement; power system protection; power system relaying; relay protection; short-circuit currents; substation protection; Brazil; anomalies detection; distribution feeder; oscillography relays; overcurrent relays; substation protection; transformer; Circuit breakers; Circuit faults; Digital relays; Impedance; Power engineering and energy; Power system faults; Power system protection; Power system relaying; Protective relaying; Substation protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
Type :
conf
DOI :
10.1109/TDC.2002.1177713
Filename :
1177713
Link To Document :
بازگشت