Title :
A protection scheme and a method for keeping a voltage balance for an 11.4-kV three-phase four-wire distribution system
Author :
Oka, Keisuke ; Motobashi, J. ; Myoga, Masahiro ; Nagasawa, Hiroshi ; Kyomoto, Sumie
Author_Institution :
Tokyo Electr. Power Co., Japan
Abstract :
An 11.4-kV three-phase four-wire distribution system can economically enhance the supply power by using most of the existing 6.6-kV distribution system facilities. In this paper, the authors made a study on securing safety and electric power quality in the 11.4-kV system by presupposing the use of a single resistance grounded neutral system based on EMTP simulations. For the safety aspect, we conducted a study on applying the major protection methods of the 6.6-kV system to the 11.4-kV system. As a result, the conditions for the application were revealed. For the electric power quality aspect, we propose the load connection phase control method and the Y-Δ connection for transformers for motors to improve the voltage unbalance. Through these measures it becomes possible to secure the quality similar to that of the existing 6.6-kV system.
Keywords :
EMTP; earthing; electric motors; phase control; power distribution control; power distribution protection; power supply quality; power system simulation; power transformers; safety; 11.4 kV; EMTP simulations; Y-D connection; distribution system facilities; electric power quality; load connection phase control method; protection scheme; safety; single resistance grounded neutral system; three-phase four-wire distribution system; voltage balance; voltage unbalance improvement; EMTP; Electric resistance; Electrical safety; Phase control; Power generation economics; Power supplies; Power system economics; Power system protection; Transformers; Voltage;
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
DOI :
10.1109/TDC.2002.1178276