DocumentCode
3161371
Title
A new numerical convolution method for impulse response analysis
Author
Sato, S. ; Harada, T. ; Wakimoto, T. ; Saeki, M.
Author_Institution
Utsunomiya Univ., Japan
Volume
1
fYear
2002
fDate
6-10 Oct. 2002
Firstpage
444
Abstract
This paper introduces a new numerical convolution algorithm, which unlike conventional techniques can compute very precise response when used in the response analysis for the lightning impulse voltage measuring system. A virtual measuring system´s unit step response, whose analytical expression is given, is used to analyse the chopped impulse voltage as well as full wave. Its impulse response, which can analytically be obtained, is compared with the numerical results processed with propose technique and with two other conventional methods. While all three techniques can attain the same precision for the full impulse analysis, only the proposed technique can maintain the precision when the front-chopped impulse voltage´s response is required.
Keywords
convolution; power system measurement; step response; transient response; voltage measurement; chopped impulse voltage; impulse response analysis; lightning impulse voltage measuring system; numerical convolution method; Algorithm design and analysis; Convolution; Helium; IEC standards; Lightning; Measurement standards; Measurement uncertainty; Measurement units; Numerical analysis; Voltage measurement;
fLanguage
English