• DocumentCode
    3162427
  • Title

    Condition assessment of on load tap changers using dynamic resistance measurements

  • Author

    Erbrink, J.J. ; Gulski, E. ; Smit, J.J. ; Chmura, L.A. ; Leich, R. ; Seitz, P.P. ; Quak, B.

  • Author_Institution
    Delft Univ. of Technol., Delft, Netherlands
  • fYear
    2010
  • fDate
    11-14 Oct. 2010
  • Firstpage
    433
  • Lastpage
    436
  • Abstract
    Resistance measurements on power transformers are a widely accepted method for finding winding defects. Continuity of the tap changer contacts can also be checked when the on-load tap changer (OLTC) is operated during the resistance measurement. Resistance measurements that also record the resistance during OLTC operation are called dynamic resistance measurements. This off-line diagnostic method can be used during regular maintenance to assess the condition of OLTC parts not accessible for inspection. Besides condition assessment of inaccessible parts of the OLTC, this method can also be used to detect maintenance errors that could lead to failure. In particular, these measurements are very helpful in finding contact discontinuity, mechanical defects that influence the operation of the tap changer contacts, problems with the switch time and the transition resistors and can find contact degradation in an early stage.
  • Keywords
    electric resistance measurement; power transformers; condition assessment; dynamic resistance measurements; on-load tap changer; power transformers; Contact resistance; Current measurement; Degradation; Electrical resistance measurement; Resistance; Switches;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2010 International Conference on
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    978-1-4244-8283-2
  • Type

    conf

  • DOI
    10.1109/ICHVE.2010.5640735
  • Filename
    5640735