Abstract
This paper presents results from laboratory experiments preformed in order to evaluate different methods for quality assurance of polymeric insulated HVDC cables. Samples of model cables were prepared, equipped with 1.5 mm thick XLPE insulation, containing insulating and conductive spherically shaped particle inclusions with diameters of 250, 140 or 80 μm, distributed at the inner semi-conductor interface. The results indicates that the 0.1 Hz VLF test voltage needs to be 2 to 3 times higher than at 50 Hz power frequency in order to eliminate the same defects within a comparable time.
Keywords
HVDC power transmission; XLPE insulation; power cable insulation; quality assurance; quality control; VLF test voltage; XLPE insulation; conductive spherically shaped particle inclusion; extruded HVDC cable; model cable contamination; polymeric insulated HVDC cable; quality assurance; quality control; semiconductor interface; size 1.5 mm; Breakdown voltage; Electric breakdown; HVDC transmission; Insulation; Mechanical cables; Testing; Time frequency analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location
New Orleans, LA
Print_ISBN
978-1-4244-8283-2
Type
conf
DOI
10.1109/ICHVE.2010.5640845
Filename
5640845
Link To Document