Transformer inrush mitigation using controlled switching of a 500-kV circuit breaker
Author :
Barnett, R. Paul ; Nelson, Jeffrey H.
Author_Institution :
Power Syst. Oper., Tennessee Valley Authority, Chattanooga, TN, USA
fYear :
2010
fDate :
11-14 Oct. 2010
Firstpage :
81
Lastpage :
84
Abstract :
This paper presents post event analyses of three inrush events that caused relay misoperation. It then presents the results of an EMTP study that illustrates the degree to which different techniques can mitigate the transformer inrush transient and compares this to the predicted performance of closing resistors in an identical application. It demonstrates that controlled switching of a transformer adequately mitigates inrush transients.
Keywords :
EMTP; circuit breakers; power transformer protection; EMTP; circuit breaker; controlled switching; transformer inrush mitigation; voltage 500 kV; Chaos; Magnetic flux; Saturation magnetization; Surges; Switches; TV;