DocumentCode :
3164524
Title :
Identification of key circuit parameters for the initiation of ferroresonance in a 400-kV transmission system
Author :
Ang, Swee Peng ; Peng, Jinsheng ; Wang, Zhongdong
Author_Institution :
Univ. of Manchester, Manchester, UK
fYear :
2010
fDate :
11-14 Oct. 2010
Firstpage :
73
Lastpage :
76
Abstract :
In this paper, the parameters that caused the onset of fundamental (Period-1) ferroresonance upon a 400 kV transmission system are investigated. After validating the developed simulation model by comparing the ferroresonance field test records (voltage and current) with the simulation waveforms, network parameters in particular the capacitances of line are studied. The overall studies suggest that the circuit-to-circuit capacitors dominate the onset of the ferroresonance phenomena whereas the ground and line-to-line capacitors supply additional discharging currents to the core. The study was performed using a computer simulation package called ATPDraw.
Keywords :
discharges (electric); ferroresonance; potential transformers; power capacitors; power transmission; circuit-to-circuit capacitors; discharging currents; ferroresonance; line-to-line capacitors; network parameters; simulation waveforms; transmission system; voltage 400 kV; Capacitance; Capacitors; Ferroresonance; Integrated circuit modeling; Power transformers; Power transmission lines; Transformer cores;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location :
New Orleans, LA
Print_ISBN :
978-1-4244-8283-2
Type :
conf
DOI :
10.1109/ICHVE.2010.5640861
Filename :
5640861
Link To Document :