DocumentCode
3166970
Title
Lightning protection in telecommunication buildings
Author
Shintaku, Mikio ; Kawakubo, Masayuki ; Kishimoto, Yasuo ; Minakuchi, Kenichi ; Ochiai, Akio
Author_Institution
Service Promotion Dept., NTT Power & Building Facilities Inc., Tokyo, Japan
fYear
1998
fDate
1998
Firstpage
697
Lastpage
702
Abstract
In this paper, we describe lightning protection systems, such as the grounding bus and buried ground ring system in microwave relay stations and a new grounding system, for telecommunication structures that have electrically sensitive switching equipment installed. We developed a method and a device for determining the route of grounding wires in existing structures. We describe how the installation of a variable resistor in parallel to an interconnecting wire can eliminate a sudden change in current or voltage when an inadequately bonded grounding wire has to be cut. We also developed a method for evaluating the efficacy of adding new lightning countermeasures to existing buildings. This method involves determining the transmission characteristics of a simulated lightning surge before and after the addition of the countermeasure
Keywords
earthing; lightning protection; microwave links; radio repeaters; surge protection; surges; buried ground ring system; electrically sensitive switching equipment; grounding bus; grounding wires route; interconnecting wire; lightning protection; lightning protection systems; microwave relay stations; simulated lightning surge; telecommunication structures; variable resistor; Bonding; Buildings; Grounding; Lightning protection; Microwave devices; Protective relaying; Resistors; Telecommunication switching; Voltage; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1998. INTELEC. Twentieth International
Conference_Location
San Francisco, CA
Print_ISBN
0-7803-5069-3
Type
conf
DOI
10.1109/INTLEC.1998.793634
Filename
793634