• DocumentCode
    3167097
  • Title

    UPS topology for powering fiber-coaxial networks

  • Author

    Pinheiro, H. ; Jain, P. ; Joos, G.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Concordia Univ., Montreal, Que., Canada
  • fYear
    1998
  • fDate
    1998
  • Firstpage
    746
  • Lastpage
    753
  • Abstract
    A single-phase uninterruptible power supply (UPS) topology suited for powering hybrid fiber-coaxial networks is presented in this paper. The main features of the proposed UPS are: (i) galvanic isolation for the input, battery and output from each other; (ii) zero voltage switching at the high frequency converters under all operating conditions; (iii) high input power factor without dedicated power factor correction stage; (iv) low current ripple in the battery; and (v) high quality output waveform. In the paper, a description and analysis of the UPS is presented and experimental results are given to demonstrate the performance of the proposed UPS
  • Keywords
    coaxial cables; harmonic distortion; optical fibre networks; power conversion harmonics; switching circuits; telecommunication power supplies; uninterruptible power supplies; UPS topology; current ripple; galvanic isolation; high frequency converters; hybrid fiber-coaxial networks; input power factor; operating conditions; output waveform quality; power supply; single-phase uninterruptible power supply; zero voltage switching; Batteries; Frequency conversion; Galvanizing; Network topology; Performance analysis; Power factor correction; Reactive power; Switching converters; Uninterruptible power systems; Zero voltage switching;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1998. INTELEC. Twentieth International
  • Conference_Location
    San Francisco, CA
  • Print_ISBN
    0-7803-5069-3
  • Type

    conf

  • DOI
    10.1109/INTLEC.1998.793644
  • Filename
    793644