  • Abstract
    Four distinct high frequency transformer uninterruptible power supplies for powering fiber-coaxial networks topologies are presented and compared in this paper. All the considered UPS topologies have isolation between the input, the output and the battery, therefore, providing safety and flexibility in the selection of the battery voltage and grounding. It has been found that the series-parallel resonant based UPS with capacitive output filter is a strong candidate since it requires just one isolation transformer and it presents high efficiency in both the line operating mode and backup mode
  • Keywords
    high-frequency transformers; hybrid fibre coax networks; telecommunication power supplies; uninterruptible power supplies; UPS topologies; ZVS; backup mode; battery voltage selection; capacitive output filter; grounding; high efficiency; high frequency transformers; hybrid fiber-coaxial networks; line operating mode; power supply; safety; series-parallel resonant based UPS; uninterruptible power supplies; zero voltage switching; Batteries; Filters; Frequency conversion; Hybrid fiber coaxial cables; Network topology; Resonance; Safety; Transformers; Uninterruptible power systems; Zero voltage switching;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunication Energy Conference, 1999. INTELEC '99. The 21st International
  • Conference_Location
    Copenhagen
  • Print_ISBN
    0-7803-5624-1
  • Type

    conf

  • DOI
    10.1109/INTLEC.1999.794065
  • Filename
    794065