Title :
Grid synchronization control without AC voltage sensors
Author :
Zhu, Huibin ; Arnet, Beat ; Haines, Lance ; Shaffer, Edward ; Lai, Jih-Sheng
Author_Institution :
Solectria Corp., Woburn, MA, USA
Abstract :
To improve the cost and reliability of utility-tied PWM inverter, this paper investigates an AC voltage sensorless grid synchronization control, either in grid-parallel inverter mode or in boost PFC rectifier mode. Based on d-q coordinate, the sensorless technique utilizes an AC line voltage estimator and an angle-searching algorithm. By commanding a positive or negative d-axis current, the fast current loop regulator controls a bidirectional power flow. The method can detect when the grid is gone, as a possible built-in anti-islanding function. Experiments verified the validity of the proposed method.
Keywords :
PWM invertors; electric current control; load flow; power factor correction; power system control; rectifying circuits; reliability; synchronisation; AC line voltage estimator; AC voltage sensorless grid synchronization control; AC voltage sensors; PFC rectifier mode; angle-searching algorithm; anti-islanding function; bidirectional power flow; d-axis current; fast current loop regulator; grid synchronization control; reliability; utility-tied PWM inverter; Circuits; Control systems; Costs; Frequency synchronization; Motor drives; Pulse width modulation inverters; Rectifiers; Sensor systems; Sensorless control; Voltage control;
Conference_Titel :
Applied Power Electronics Conference and Exposition, 2003. APEC '03. Eighteenth Annual IEEE
Conference_Location :
Miami Beach, FL, USA
Print_ISBN :
0-7803-7768-0
DOI :
10.1109/APEC.2003.1179210