• DocumentCode
    3172483
  • Title

    Grid synchronization control without AC voltage sensors

  • Author

    Zhu, Huibin ; Arnet, Beat ; Haines, Lance ; Shaffer, Edward ; Lai, Jih-Sheng

  • Author_Institution
    Solectria Corp., Woburn, MA, USA
  • Volume
    1
  • fYear
    2003
  • fDate
    9-13 Feb. 2003
  • Firstpage
    172
  • Abstract
    To improve the cost and reliability of utility-tied PWM inverter, this paper investigates an AC voltage sensorless grid synchronization control, either in grid-parallel inverter mode or in boost PFC rectifier mode. Based on d-q coordinate, the sensorless technique utilizes an AC line voltage estimator and an angle-searching algorithm. By commanding a positive or negative d-axis current, the fast current loop regulator controls a bidirectional power flow. The method can detect when the grid is gone, as a possible built-in anti-islanding function. Experiments verified the validity of the proposed method.
  • Keywords
    PWM invertors; electric current control; load flow; power factor correction; power system control; rectifying circuits; reliability; synchronisation; AC line voltage estimator; AC voltage sensorless grid synchronization control; AC voltage sensors; PFC rectifier mode; angle-searching algorithm; anti-islanding function; bidirectional power flow; d-axis current; fast current loop regulator; grid synchronization control; reliability; utility-tied PWM inverter; Circuits; Control systems; Costs; Frequency synchronization; Motor drives; Pulse width modulation inverters; Rectifiers; Sensor systems; Sensorless control; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Applied Power Electronics Conference and Exposition, 2003. APEC '03. Eighteenth Annual IEEE
  • Conference_Location
    Miami Beach, FL, USA
  • Print_ISBN
    0-7803-7768-0
  • Type

    conf

  • DOI
    10.1109/APEC.2003.1179210
  • Filename
    1179210